100Kva Power Transformers Must Provide Power To The Auxiliaries And Must Have The Following Characteristics: Quantity: 08 Nominal Power In Kva: 100 Primary Nominal Voltage V ± 5%: 5,500 (Three-Phase) Secondary Voltage V: 220V/380V (Three-Phase) Load Voltage At Cos (Phi) = 0.85: 380V Between Phases And 220V Between Phase And Neutral Primary Winding Insulation Voltage: ≥ 17.5 Kv Frequency In Hz ± 2.5%: 50 Insulation: Oil Type: Outdoor Number Of Primary Terminals: 3 Cooling: Oil Bushing Insulation: ≥ 17.5 Kv Assigned Voltage: 12 Kv Power Frequency Withstand Voltage: 28Kv Impulse Withstand Voltage: 75Kv Number Of Secondary Terminals: 4 Short Circuit Voltage: 4% Coupling: Dyn11 Primary Coupling: Delta Secondary Coupling: Star With Neutral Output The Transformer Must Be Protected Against Any Climatic Influence Porcelain Hv Bushing. Protective Enclosure: Yes Test Sheets: Yes Accuracy Class: +/- 5% Supplier Assistance At First Test And Before Commissioning: Yes The Transformer Must Be Protected Against Any Climatic Influence The Power Transformer Must Be Equipped With D.G.P.T.2 Relays. The Power Transformer Must Be In A Metal Enclosure Ensuring Their Protection Against Any Direct Contact And Also Their Environmental Protection Ip 45 The Power Transformer Must Be Equipped With A Primary And Secondary Coil Heating Detector. The Transformer Must Be Equipped With A Heat Extractor To The Outside Standards: Heating, Tolerances, Test Voltages, According To Standards Ute C 52 100 And Iec Pub. 76 Documentation In French And In 03 Copies: Use And Maintenance Manual (EXPIRED)